Skip to main content

HITACHI P1 VFD Installation

{{@672}}

hitachi_p1-midrange_14.jpg


VFD Control Type

There are 3 different ways a Hitachi VFD may be connected to MachMotion control: Ethercat, TCP Modbus, or Hardwired. Use the following procedure to determine which method your VFD uses. Then in each section of the manual go to that control method for information on how to program or connect it. 

On the menu bar of the MachMotion software, click Configure -> Control, then select the Output Signals tab.

Scroll down about 2/3s the list to the Spindle section. The Device that is selected for Spindle Fwd and / or Spindle Rev shows how the spindle is controlled. Use the pictures below to identify which method is used.

Ethercat

Ethercat.PNG

TCP Modbus

(Waiting for Picture - but the device should be Hitachi-P1_X)

Hardwired

For a hardwired VFD, it could be controlled through a Beckhoff Device OR an Apollo III. 

Beckhoff.PNG


Wiring

Control Cable: The VFD Control cable is the green Ethernet cable that runs from the Yaskawa VFD to the Control PC as shown in Figure 1. Or if you have an Apollo III motion controller, connect the VFD control cable into Ethernet 1 Port on the Apollo III. 

(Figure 1 Ethernet Connection to Control PC)

Spindle Motor: Connect your spindle motor to the terminals labeled U/T1,V/T2, and W/T3 as shown in Figure 2. If your spindle moves the wrong direction when you turn it on, just swap any three of the (U,V,W) leads.

P1_Wiring.PNG

(Figure 2 Spindle Motor Connections)

Brake Resistor: Connect your brake resistor by placing the two wires on the RB and P terminals as shown in Figure 3.
(Note: If needed to extend the wires use High Temp rated wire.)

Mount Resistor: Mount the resistor to the cabinet. Wire as shown in Figure 3.

P1_Braking_Resistor.PNG

(Figure 3 Resistor Connections)

Programming

Changing Parameters on the drive through the front panel

Use the F1 key to enter into menu mode.

P1_Buttons.PNG

P1_Functions.PNG

1. Modbus Installation

Setup the IP Address

To modify the IP address follow these steps:

  1. F1 (menu)
  2. Select 01 Scroll mode with the Center button
  3. Press the Down Arrow multiple times until you highlight o:Option Card
  4. Select o:Option Card with the Center button
  5. Press F2 (Next Gr) multiple time until you get to the group oL-01 IPv4 IP address
  6. Press the Down Arrow multiple times until you highlight oL-03 IPv4 IP address
  7. Select oL-03 IPv4 IP address with the Center button
  8. Using the Up and Down, Left and Right Arrows set the IP Address group 3 to 208
  9. Press F2 (Save)
  10. Repeat steps 6 to 9 to set the remaining address groups

Before the Control can connect to the VFD these parameters need to be set.  On default you should only need to set the ones in bold.

 ParametersDescriptionDefaultRange
oL-01IPv4 IP Address (1)192

IP Address

oL-02IPv4 IP Address (2)168

IP Address

oL-03IPv4 IP Address (3)208

IP Address

oL-04IPv4 IP Address (4)95

IP Address

oL-09IPv4 Default Gateway (1)192

IP Address

oL-10IPv4 Default Gateway (2)168

IP Address

oL-11IPv4 Default Gateway (3)208

IP Address

oL-12IPv4 Default Gateway (4)1

IP Address


Open the Configurable Parameters

To program the VFD you will need to utilize the Parameters.  Follow the next few steps to find the Hitachi parameters.
{{@1106}}
While in the Parameters Type "Hitachi" in the search field as shown in Figure 5. This will populate the parameters for the Hitachi P1 VFD as shown below).

P1_MM_Parameters.PNG

(Figure 5 Default Parameters)

Enable the VFD

For a main spindle, set Control Source to Mach and Modbus Control Enabled to Yes. For any other spindle like a grind wheel, regulating wheel, or sub spindle, set Control Source to Auxiliary and Modbus Control Enabled to Yes.

2. Hitachi VFD EtherCAT Installation:

To set up the Hitachi VFD to be commanded by EtherCAT you will need to modify 2 parameters:

Parameter

DescriptionDefault ValueDesired Value

AA101

Main Speed Source_M1 (Term.[Ai1])9 (Option-1)
AA111Run-cmd. Source_M10 (Term.[FW]/[RV])4 (Option-1)


The RapidPath plugin controls (writes to) some parameters for operation. If you change the value of any of them, your change will be overwritten.

Parameter
CC-01
CC-02
CC-06
CC-07
This can be done automatically via Mach.

Go to Configure | Plugins | RapidPath - MachMotion:

image-1654551631993.png

Select the Other Devices tab, Click on the Hitachi VFD in the dropdown on the left and then select the Device Parameters at the bottom of the page:

image-1654551587280.png

From here you can click the Load from File button. Navigate to the Plugins/Dependencies/RapidPath/DriveConfig/Hitachi_VFD directory and select the file: Hitachi_Install_EtherCAT_I_O_device.drvprm.

image-1654551977607.png

Once it has loaded the parameter values, those which were updated, will be highlighted in green:

image-1654552327546.png

Click Write Changes button to save the updates to the drive.

You will need to recycle the drive for the change to the fan to take immediate effect.

3. Hitachi VFD Hardwired Analog Installation:

Programming

To be able to program the Hitachi VFD you will either need to change the parameters physically on the VFD or with the Hitachi ProDrive Next software. 

Hitachi Software Downloads

- Software requirements: Mini USB Cable connected to the VFD and the computer that will be doing the programming.


HITACHI P1 Parameters

Set up the motor parameters 

Find your motor nameplate and enter in the parameters based on the table below.

If you cannot locate the motor’s base frequency, the name plate should tell you how many poles there are on the motor. You can also call the motor manufacturer to figure out the number of poles. Using the motor’s maximum RPM and its number of poles, you can calculate the base frequency with the formula below:

Base Frequency = Max RPM * Number of Poles / 120

 

 ParametersDescriptionDefaultRange
AC120Motor Accel. Time4 Seconds0.0 to 3600.0 Seconds
AC122Motor Decel. Time3 Seconds0.0 to 3600.0 Seconds
Hb102Motor Rated KWs1.5 kW0.00 to 650.00 kW
HB103Number Of Motor Poles 4 Poles2 to 12 Poles
HB104Motor Base Frequency60 Hz1.0 to 590.0 Hz
HB105Motor Max Output Frequency60 Hz1.0 to 590.0 Hz
HB106Motor Max Output Voltage220 Volts1-510 Volts
HB108Motor Rated Current5 Amps 10% to 200% of drive rated current
HB130Motor Min Output Frequency 0.5 Hz0.1 to 590.0 Hz

You can also modify the fan settings with this parameter.

Parameter

DescriptionDefault ValueDesired Value

bA-70

Cooling fan control0 (Always on)

2 (Temperature controlled)

 

Overspeed a Motor

If you want to command your spindle motor or grinding wheel to go faster than the base frequency, command the spindle to go max RPM and use a tachometer to measure the speed. Then use the following formula to calculate your new Max Output Frequency (Hb105):

Desired Max RPM * Current Max Frequency / Current Max RPM = New Max Frequency 

For example, if your Current Max Frequency is 60 and you measure the spindle runs 1030 RPM but you actually want it to go 1515 RPM, calculate your new Max Frequency as follows: 

1515 * 60 / 1030=88 Hz. 

Make sure to recalibrate your RPM feedback and your spindle speed as both shown below. 



Calibrate Spindle Speed

If your P1 is setup as a Mach spindle (under MachMotion Parameters), click on Configure -> Control at top of the Mach screen. Then select the "Spindle" tab shown in Figure 7. Set your max spindle RPM for each spindle range here. 

(Figure 7 Spindle Tab)


If your VFD is enabled as an Auxiliary spindle (under MachMotion Parameters), set the Auxiliary Control Max RPM to the max RPM of the motor.

image-1589904534449.png


Calibrate RPM Feedback

If your VFD is enabled as a Mach spindle (and there can only be one enabled at a time), follow the procedure below. 

You will need to scale your emulated RPM feedback in the Mach software. Calculate your feedback ratio as follows:

  • Max Spindle RPM / 3600 = Feedback Ratio

Then while the control is disabled follow the next few steps:

Step 1: Click on Configure -> Control at top of the Mach screen. Then select the "Spindle" tab shown in Figure 7.

(Figure 7 Spindle Tab)

Step 2: Enter in the value you calculated in FeedBack Ratio from the calculation you have done for Spindle Gear 1 as shown in Figure 8.

FeedBack Ratio for Spindle Gear 1

(Figure 8 Enter Feedback Ratio)

Troubleshooting

Alarms

If you were to get an alarm on the VFD you will receive a message on the computer screen from the Global Message System. In the description of the alarm it will describe the necessary steps to try to resolve the alarm.


Setup Verification

To test any modbus VFD, review the following items to confirm it is setup correctly:

Does the VFD run the spindle? The VFD RUN light should be on solid when it is up to speed. If it isn't, the VFD is not programmed correctly. 

Does the RPM change when you change the spindle speed on the control?

Does the VFD go both directions?

If you disconnect the VFD control cable does the control time out with a VFD Disconnected Error?

Is the RPM feedback correct? 

Does up to speed and at speed work correctly inside the control? 


Appendix

Apollo III 

Make sure the VFD is powered all the time. Otherwise the VFD will not connect correctly. 


Wire the Estop circuit as shown below: 

image-1596118445088.png



{{@677}}