2000 Series Waterjet Setup Manual

Mach Setup

Jet Setup

Configure the number of jets you need and your default delays. 

image.png

 

IO Setup

Virtually every waterjet will need some of following signals. Map each of the ones you need to the correct output. 

image.png

Name Function Configuration
Jet Abrasive Output(s) Turns on and off abrasive for the corresponding jet. Map it to the correct output signal in Mach.
Jet High Pressure Output(s) Turns on and off high pressure for the corresponding jet. Also called things like UHP On/On valve.   
Jet Pressure Output(s) Turns on and off the actual jet. Often called Water On or Jet On. 
Jet Pump Output This turns on the actual intensifier pump. If using a PLC this should trigger the PLC to start the intensifier. Often called Intensifier. 


Some waterjets may have some of these more advanced IO. This is more for when the intensifier is controlled inside the MachMotion PLC. 

Outputs

Setupinthe
Name Function Configuration
HP Bleeddown Valve When the jet turns off this valve must open to let the pressure out of the line. Should always be off when the pumpintensifier is off.  Setup in the PMC. 
Cooling Water Shutoff Valve 

This function keeps the pump cool. Should always be on when the pump is on. 

Setup in the PMC. 
Filtered Water Shutoff/ ValveWater InletThis sends water to the intensifier. It must be on before the intensifier is turned on or it could blow it up. 

Water On SolenoidJet on?
PMC.
INTENSIFIER LEFT SHIFT SOLENOID
Moves the hydraulic cylinder to the left.
Must be wired to the PLC and programmed in the PLC. 
INTENSIFIER Right SHIFT SOLENOID
Moves the hydraulic cylinder to the right.
Must be wired to the PLC and programmed in the PLC. 
BOOST PUMP




Inputs

in
Name Function Configuration
Garnet Empty Tells the operator when to refill the garnet

 Setup in GMS.

INTENSIFIER LEFT CHECK VALVE
OVERTEMP

Setup


in GMS.
INTENSIFIER RIGHT CHECK VALVE
OVERTEMP


Setup in GMS. 

INTENSIFIER LEFT SHIFT SENSOR

Must be wired to the PLC and programmed in the PLC. 

INTENSIFIER RIGHT SHIFT SENSOR

Must be wired to the PLC and programmed in the PLC. 

INLET WATER PRESSURE WARNING


Setup in GMS.

INLET WATER PRESSURE SHUTDOWN
This input measures the water pressure at the intensifier after the water inlet motor or pump is on. It must be up to pressure before the intensifier can turn on. 


Setup in GMS. AND must be wired to the PLC to prevent the Intensifier from turning on until this input is off. 

HP BLEEDDOWN OVERTEMP WARNING


Setup in GMS.

HYDRAULIC OIL OVERTEMP WARNING


Setup in GMS.

HYDRAULIC OIL OVERTEMP
SHUTDOWN


Setup in GMS.

HYDRAULIC OIL LEVEL SHUTDOWN


Setup
INTENSIFIER ON??





GMS.

 

 

Some waterjets have a servo controlled Abrasive. For that use these settings:

image.png

Analog Inputs and Outputs

You may have analog inputs and outputs used for setting pressure or garnet speed. Often you put them on the main screen of the waterjet. Configure them according to the device you are using (Siemens PLC Setup, or Rapidpath Beckhoff Setup). 

image.png

 

image.png

 

 

PLC Setup

If the intensifier is controlled by the MachMotion PLC, then you need to program the PLC.

Before programming the PLC, make sure to test all the machine IO in Mach. That allows you to easily confirm the IO is working. 

Then program the PLC with our default PLC program for waterjets. It is located under development SVN: C:\Mach4_Development\PLCs\PLC-Program-Generic-Waterjet-Intensifier-Pump-Control_V15 . 

MapNow you need to remove the IOoutputs in Mach so only the PLC can write to them. 

Open the Modbus window and delete the outputs that can only be controlled by the PLC: 

image.png

For example, remove intensifier left solenoid and right solenoid that are mapped to Q0.0 and Q0.1 by clicking on output and then selecting Remove a Modbus Function button. 

image.png

Update the PLC tags inside the PLC based on how this machine is wired. Here are the main signals that must be wiredaccording to the PLC:schematic you have. 

image.png