Yaskawa V1000 Setup Procedure

Change IP Parameters On V1000

Correct parameters:

  • F7-13-0
  • F7-03-208
  • F7-04-90
  • B1-01-3
  • B1-02-3

Follow these instructions to change parameters in the drive:

1) Press down arrow until screen reads "PAR." Press Enter.

2. Press down arrow the screen reads "F7-01."

3. Press ">Reset" two times until "01" is flashing.

4. Press the up arrow until the value reads "13." Press Enter.

5. Use the arrow to change the value to "00." Press Enter. The screen will flash "End" and go back to the previous screen.

6. Use the moves in 4 and 5 to change the remaining parameters:

       -Change F7-03 to "208"

       -Change F7-04 to "90"

7. Press ESC until the "F" on the screen is flashing. Then, press the down arrow until the screen reads "b1-01."

8. Use the moves in 3 to 5 to change the remaining parameters:

       -Change B1-01 to "3"

       -Change B1-02 to "3"

9. Power cycle control and enclosure to reset VFD.

 

Install Yaskawa DriveWizard and Change IP

1) On the MachMotion server, Go to Production->Products->Spindles->VFDs->Yaskawa->V1000->sw.dw.30.

2) Move "setup" to the desktop of the controller and double click to install.

3) After running the install, open "DriveWizard Industrial." Then, click on "Drive Selection & Communication Setup."

4) Change the first drop down to V1000. Select "Ethernet" option. Click "Modify" and change IP address to 192.168.208.90 

5) Click "Connect to Drive / Go Online."

 

Write Base Parameters to VFD

1) On the MachMotion server, Go to Production->Products->Spindles->VFDs->Yaskawa->V1000->Drive Parameters.

2) Drag "V1000 RPKM YDWI Project" to the desktop of the controller.

3) Once connected to the drive, click on "Open Project."

4) Select "V1000 RPKM YDWI Project" that you just placed on the desktop.

5) Once loaded, click "Write Parameters" to send to VFD. 